Yokogawa TC/mV Input Module AAT145-S00
STANDARD SPECIFICATIONS of AAT145-S00
TC/RTD Input Modules (Isolated Channels)
AAT145, AAR145 These modules receive signals from mV, thermocouple (TC), RTD, and potentiometer (POT), and they are isolated between the field and the system as well as in between each channel. They can be used in dual-redundant configuration.
Items | Specifications | |
Model | AAT145 | AAR145 |
Number of input channels | 16, isolated channels | 16, isolated channels |
Input signal |
TC: JIS C1602:1995 (*1), IEC584:1995 Type J, K, E, B (*2), R, S, T, N mV: -100 to 150 mV, -20 to 80 Mv |
RTD: JIS C1604:1997 (*3), IEC751:1995 Pt100 (3-wire type) POT: Total resistance 100 Ω to 10 kΩ Span resistance: 50 % or larger of total resistance |
Switching input signals | TC/mV can be set individually for CH1 to CH16 | RTD/POT can be selected individually for CH1 to CH16. |
Allowable input voltage | ±5 V | ±5 V |
Withstanding voltage |
Between input and system: 500 V AC (for single card: 1500 V AC), For 1 minute Between input channels: 200 V AC, For 1 minute |
|
Input resistance | Power ON 1 MΩ or larger | |
Power OFF 1 MΩ or larger | ||
Accuracy | ±40 μV |
RTD: ±150 mΩ POT: ±0.2 %/FS |
Allowable total resistance of signal source plus wiring |
1000 Ω or less | 150 Ω or less (wiring resistance per wire) (*4) |
Effect of allowable signal source resistance (1000 Ω) |
±20 μV | |
Reference junction compensation accuracy |
±1 °C (*5) (6) | |
Measurement current | RTD: 1 mA | |
Data update period | 1 s | |
Burn-out |
All channels can be set together. Setting: not available/available (UP/DOWN) Detection time: 60 s |
|
Temperature drift | ±80 μV/10 °C |
RTD: ±0.3 Ω/10 °C POT: ±0.4 %/10 °C |
Maximum current consumption |
350 mA (5 V DC) | 350 mA (5 V DC) |
Weight | 0.3 kg | |
External connection | Dedicated cable (KS1) | Dedicated cable (KS8/AKB335) |
Yokogawa TC/mV Input Module AAT145-S00
MODEL AND SUFFIX CODES AAT145-S00
Description | ||
Model | AAT145 | TC/mV Input Module (16-channel, Isolated channels) |
Suffix Codes |
-S | Standard type |
5 | With no explosion protection | |
E | With explosion protection | |
0 | Basic type | |
3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option |