IN STOCK Yokogawa DCS Module AAI543-S50/K4A00 Analog Input Module
	
STANDARD SPECIFICATIONS
	   Current/Voltage Input Modules (Non-Isolated)
	  These modules provide 16 inputs of mainly 4 to 20 mA DC or 1 to 5 V DC standardized signals from 2-wire/4-wire transmitters.
	  They can be used in dual-redundant configuration.
Current Input Modules (Isolated)
AAI143 provides 16 inputs of 4 to 20 mA signal. It can be used in dual-redundant configuration.
| Items | Specifications | 
| Model | AAI143 (*1) | 
| Number of input channels | 16, isolated | 
| Input signal | 4 to 20 mA | 
| Allowable input current | 24 mA | 
| Input resistance | Power ON 270 Ω (20 mA) to 350 Ω (4 mA) (*2) | 
| Power OFF 500 kΩ or larger | |
| Accuracy | ±16 μA | 
| Data update period | 10 ms | 
| Transmitter power supply | 19.0 V or higher (at 20 mA) 25.5 V or less (at 0 mA) (output current limit: 25 mA) (*5) | 
| Setting of 2-wire or 4-wire transmitter | For each channel by setting pin | 
| Drift due to ambient temperature change | ±16 μA/10 C | 
| Maximum current consumption | 230 mA (5 V DC), 540 mA (24 V DC) | 
| Weight | 0.3 kg | 
| External communication | Pressure clamp terminal, MIL connector cable, dedicated cable (KS1) | 
| HART communication (*3) | Available | 
Yokogawa Analog Input Module AAI143
EXTERNAL DIMENSIONS of AAI143
	
Yokogawa Analog Input Module AAI143-H50
MODEL AND SUFFIX CODES AAI143-H50
| Description | ||
| Model | AAI143 | Analog Input Module (4 to 20 mA, 16-channel, Isolated) | 
| -S | Standard Type | |
| -H | With digital communication (HART protocol) | |
| 
				Suffix Codes  | 
			5 | With no explosion protection | 
| E | With explosion protection | |
| 0 | Basic type | |
| 3 | With ISA Standard G3 option and temperature (-20 to 70 °C) option | |
| 
				Option Codes  | 
			/K4A00 | With KS Cable Interface Adapter [Model : ATK4A-00] | 
| /A4S00 | With Pressure Clamp Terminal Block for Analog [Model : ATA4S-00] | |
| /A4S10 | With Pressure Clamp Terminal Block for Analog (surge absorber) [Model : ATA4S-10] | |
| /A4D00 | With Dual Pressure Clamp Terminal Block for Analog [Model : ATA4D-00] | |
| /A4D10 | With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model : ATA4D-10] | |
| /CCC01 | With Connector Cover for MIL Cable [Model : ACCC01] | 
AAI143 Analog Input Module (4 to 20 mA, 16-channel, Isolated)
AAI143-S50/K4A00, AAI143-S50/A4S00, AAI143-S50/A4S10, AAI143-S50/A4D00, AAI143-S50/A4D10, AAI143-S50/CCC01,
AAI143-S53/K4A00, AAI143-S53/A4S00, AAI143-S53/A4S10, AAI143-S53/A4D00, AAI143-S53/A4D10, AAI143-S53/CCC01,
AAI143-SE0/K4A00, AAI143-SE0/A4S00, AAI143-SE0/A4S10, AAI143-SE0/A4D00, AAI143-SE0/A4D10, AAI143-SE0/CCC01,
AAI143-SE3/K4A00, AAI143-SE3/A4S00, AAI143-SE3/A4S10, AAI143-SE3/A4D00, AAI143-SE3/A4D10, AAI143-SE3/CCC01,
AAI143-H50/K4A00, AAI143-H50/A4S00, AAI143-H50/A4S10, AAI143-H50/A4D00, AAI143-H50/A4D10, AAI143-H50/CCC01,
AAI143-H53/K4A00, AAI143-H53/A4S00, AAI143-H53/A4S10, AAI143-H53/A4D00, AAI143-H53/A4D10, AAI143-H53/CCC01,
AAI143-HE0/K4A00, AAI143-HE0/A4S00, AAI143-HE0/A4S10, AAI143-HE0/A4D00, AAI143-HE0/A4D10, AAI143-HE0/CCC01,
AAI143-HE3/K4A00, AAI143-HE3/A4S00, AAI143-HE3/A4S10, AAI143-HE3/A4D00, AAI143-HE3/A4D10, AAI143-HE3/CCC01
	  Yokogawa Analog Input Module AAI143-H50 AAI143-S50
	 
			
		
	
							
											
											